Hostdoggy
relies
on
Savvis
for
fast
and
efficient
data
transport,
their
reliability
is
unsurpassed.
The
Fort
Worth
Texas
Savvis
facility
contains thousands of square feet of climate controlled
data center
space. Redundancy is installed at every level, power is conditioned and kept constant by Powerware centralized UPS solutions backed by
CAT diesel power generation
technology.
Savvis
serves
more
than
8,000,000
clients
worldwide.
Savvis
provdes
Wall
Street
(NYSE)
with
all
of
it's
communication
needs.
|
Savvis
Datacenter
Overview:
- 153,800
sq
ft
building
- No
advertising
of
SAVVIS
name
(plain
wrapper)
- Interior
and
exterior
security
managed
24/7
by
permanently
assigned
staff
of
Wackenhut
guard
Zoned
access
throughout
Data
Center
- Biometric
hand
scanner
requires
ID
card
access
and
hand
geometry
measurements
- Customer
IDC
access
and
contacts
managed
via
Siebel
- Current
government-issued
picture
ID
required
- ID
badge
and
biometric
hand
scan
to
man
trap
with
badge
reader
- Second
hand
scans
to
gain
access
to
raised
floor
Biometric
scanner
captures
3D
measurements
of
hand
Security
cameras
- Multiple
360
degree
cameras
with
10x
zoom
- More
than
100
fixed
cameras
- High
speed
recorders
with
DV
cassette
tapes
- Hard
drives
to
eliminate
down
time
for
tape
swaps
and
over
recording
- Minimum
30
day
tape
storage
Generator
power
- Backup
power
- Multiple
CAT
Diesel
2.0
megawatt
generators
Minimum
24
hour
fuel
storage
- Agreements
with
two
major
carriers
to
provide
additional
diesel
fuel
- Generators
assumes
building
load
within
20
seconds
- Generators
are
tested
on
weekly
basis
under
load.
- Tanks
are
kept
at
least
80%
full
at
all
times
Two
utility
feeds
from
independent
substations
- Diverse
paths
to
the
building
- Feeds
to
building
are
encased
in
concrete
- Fed
from
two
independent
substations
- Separate
transformers
fed
from
both
utility
sources
for
redundancy
HVAC
chiller
systems
- Hosting
space
HVAC
system
includes
(16)
AHUs
and
(16)
ACCUs
manufactured
by
Trane.
- AHUs
are
DX
type
and
located
in
the
mechanical
mezzanine;
the
ACCUs
are
located
on
the
roof.
- There
is
adequate
capacity
to
withstand
a
HVAC
unit
failure
or
an
entire
bus
failure.
Cooling
is
provided
by
both
overhead
and
under
floor
air.
- HVAC
systems
have
wetted
media
for
humidification,
VFDs
for
each
supply
fan,
exhaust
fans
to
control
building
pressure,
and
economizers
to
utilize
cool
outside
air.
- Separate
Dectron
outside
air
handling
units
provide
conditioned
air
for
the
hosting
space.
- UPS
Room
cooling
is
provided
by
Trane
RTUs
in
a
N+1
configuration.
- Node
room
cooling
is
provided
by
Liebert
DX
CRAC
units
in
a
N+1
configuration.
Network
facilities
-
Main
Node
Room
- Multiple
fiber
providers
for
diversity
-
provides
diversity
and
redundancy.
- Each
vendor
can
deliver
additional
bandwidth
capacity
with
minimal
turn-around
time
- Can
be
delivered
using
existing
‘lit’
fiber
- Fiber
pathways
into
the
Data
Center
are
truly
diverse
- Fiber
enters
building
in
steel
conduit
from
multiple
points
in
the
building

|